Field test of optical and electrical fire detectors in simulated fire scenes in a cable tunnel

  • Dian Fan
  • , Hongjun Ding
  • , Dorothy Y. Wang
  • , Desheng Jiang

Research output: Contribution to journalArticlepeer-review

Abstract

This paper presents the testing results of three types of fire detectors: electrical heat sensing cable, optical fiber Raman temperature sensing detector, and optical fiber Bragg grating (FBG) temperature sensing detector, in two simulated fire scenes in a cable tunnel. In the small-scale fire with limited thermal radiation and no flame, the fire alarm only comes from the heat sensors which directly contact with the heat source. In the large-scale fire with about 5°C/min temperature rising speed within a 3-m span, the fire alarm response time of the fiber Raman sensor and FBG sensors was about 30 seconds. The test results can be further used for formulating regulation for early fire detection in cable tunnels.

Original languageEnglish
Pages (from-to)156-161
Number of pages6
JournalPhotonic Sensors
Volume4
Issue number2
DOIs
StatePublished - Jun 2014

Keywords

  • cable tunnel
  • fire detector
  • Fire simulation
  • response time

Fingerprint

Dive into the research topics of 'Field test of optical and electrical fire detectors in simulated fire scenes in a cable tunnel'. Together they form a unique fingerprint.

Cite this